IQ 100 Series ((130/140/150) Meter
Programming the Meter Using the Front Panel
User and Installation Manual IM02601003E - September 2011 www.eaton.com 59
Understanding the % of Load Bar
The 10-segment LED bar graph at the bottom left of the IQ 100 Series front panel provides a graphic
representation of Amps. The segments light according to the load, as shown in the table below.
When the Load is over 120% of full load, all segments ash “On” (1.5 secs) and “Off” (0.5 secs).
% of Load Segment Table
Segments
Load >= % Full Load
none no load
1 1%
1-2 15%
1-3 30%
1-4 45%
1-5 60%
1-6 72%
1-7 84%
1-8 96%
1-9 108%
1-10 120%
All Blink >120%