IQ 100 Series (130/140/150) Meter Appendix B: Modbus Map
Description
1
Format Range
6
Units or
Resolution Comments
#
Reg
Modbus Address
Hex Decimal
9C4F - 9C4F 40016 - 40016 CT numerator UINT16 1 to 9999 none 1
9C50 - 9C50 40017 - 40017 CT multiplier UINT16 1, 10, 100 none 1
9C51 - 9C51 40018 - 40018 CT denominator UINT16 1 or 5 none 1
9C52 - 9C52 40019 - 40019 PT numerator UINT16 1 to 9999 none 1
9C53 - 9C53 40020 - 40020 PT multiplier UINT16 1, 10, 100 none 1
9C54 - 9C54 40021 - 40021 PT denominator UINT16 1 to 9999 none 1
9C55 - 9C56 40022 - 40023 W-hours, Positive UINT32 0 to 99999999 Wh per energy format
* 5 to 8 digits
2
9C57 - 9C58 40024 - 40025 W-hours, Negative UINT32 0 to 99999999 Wh per energy format
* decimal point implied, per energy format
2
9C59 - 9C5A 40026 - 40027 VAR-hours, Positive UINT32 0 to 99999999 VARh per energy format 2
9C5B - 9C5C 40028 - 40029 VAR-hours, Negative UINT32 0 to 99999999 VARh per energy format 2
9C5D - 9C5E 40030 - 40031 VA-hours UINT32 0 to 99999999 VAh per energy format
* see note 10
2
9C5F - 9C5F 40032 - 40032 Neutral Current UINT16 0 to 4095 amps
see Amps A/B/C above
1
9C60 - 9CA2 40033 - 40099 Reserved N/A N/A none 67
9CA3 - 9CA3 40100 - 40100 Reset Energy Accumulators UINT16
password
5
write-only register; always reads as 0 1
Block Size
:
100
Notes
1
2
3
4
5
* resolution of digit before decimal point =
units, kilo, or mega, per energy format
ASCII ASCII characters packed 2 per register in high, low order and without any termination characters.
SINT32 / UINT32
FLOAT
32-bit signed / unsigned integer spanning 2 registers. The lower-addressed register is the high order half.
SINT16 / UINT16 16-bit signed / unsigned integer.
End of Ma
p
32-bit IEEE floating point number spanning 2 registers. The lower-addressed register is the high order half (i.e., contains the exponent).
All registers not explicitly listed in the table read as 0. Writes to these registers will be accepted but won't actually change the register (since it doesn't exist).
Meter Data Section items read as 0 until first readings are available or if the meter is not in operating mode. Writes to these registers will be accepted but won't actually change the register.
Register valid only in programmable settings update mode. In other modes these registers read as 0 and return an illegal data address exception if a write is attempted.
Meter command registers always read as 0. They may be written only when the meter is in a suitable mode. The registers return an illegal data address exception if a write is attempted in an incorrect
mode.
If the password is incorrect, a valid response is returned but the command is not executed. Use 5555 for the password if passwords are disabled in the programmable settings.
Data Formats
CT = numerator * multiplier / denominator
PT = numerator * multiplier / denominator
User and Installation Manual IM02601003E -September 2011 MM-8