uto Tip-up Test Tip-up testing is used for testing power
components with voltage dependent dissipation
factor (e.g. generators) or in case a voltage
dependence is suspected and indicated by high
DF in Delta4000. The highest voltage level
used is set on main page and the voltage per
step is set on the settings page Voltage steps
can be set on the settings page
Frequency Sweep Frequency Sweep allows the user to perform a
series of tests over a frequency range. The
oltage level used is set on main page and the
oltage per step is set on the settings page. Note
that there are limitation of voltage levels at high
frequencies and low frequencies below 45 Hz
Manual
his mode allows continuous manual control of
output voltage.