48
Frequency Sweep
Delta4000 can also measure multiple frequencies in a “frequency sweep”.
Individual frequencies are defined in a list in PDB settings. The maximum
frequency range is pending the test voltage as described in the following table.
Test Voltage Maximum frequency
range
12 kV 45-70 Hz
4 kV 15-405 Hz
2 kV 8-505 Hz
1 kV 4-505 Hz
500 V 2-505 Hz
250 V 1-505 Hz
Note: Do not select the power frequency or any multiple of power frequency in a
frequency sweep, e.g. in 50 Hz networks avoid, 50, 100, 150… and in
60 Hz networks avoid 60, 120, 180…
Temperature Correction
Delta4000 offers two temperature correction methods;
Standard Temperature Correction Tables
This is the standard correction method based on tables for various components.
For power transformers the table selection is based on manufacturing year,
transformer type (sealed, free breathing etc), voltage and power rating. For
bushings the table is selected by manufacturer and type.