M
81331 Rev 01 Nov 2010
72
NOTE: Once Tests 5, 6 and 7 are completed, Line 8 will populate with values
calculated by subtracting Test 6 from Test 5. This is applicable for
values of capacitance, current and watts. Line 8 is a calculated
comparison to the direct measurements of Test 7. Values on these two
lines should be essentially the same. If they are not, re-check all
connections and verify the proper operation of the test set. If Test 7 and
Line 8 vary by more than 2%, the Insulation Rating (IR) will
automatically populate with B (Bad).
Lines 9 and 10 will automatically populate with calculated values once Tests 1-7
and all bushing tests are completed. Line 9 is a corrected value for the insulation
of the high voltage winding to the transformer tank minus the measured losses
of the high side bushings. Line 10 is a corrected value for the insulation of the
low voltage winding to the transformer tank minus the measured losses of the
low side bushings.
Bushing C1 Tests
If the transformer windings are terminated using condenser bushings, then
measurements of the C1 insulation on each bushing are generally made. The
bushing insulation C1 is internal and is the insulation between the bushing center
Page view 79