VFD-B Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-50
70%
100%
Output
Voltage
During the auto energy-saving
operation, it will adjust the output
voltage according to the output
power. The maximum output
voltage can be 30% lower than
the normal output voltage.
Output Frequency
08 - 16
Automatic Voltage Regulation (AVR)
Factory Setting: 00
Settings 00 AVR function enabled
01 AVR function disabled
02 AVR function disabled for deceleration
The rated voltage of motor is usually AC220V/200V, 60Hz/50Hz and the input voltage of
AC drive is AC 180V ~ 264V, 50Hz/60Hz. When AC drive runs without AVR function, if
input power is AC 250V and the output voltage to motor will also be AC 250V. The
voltage exceeds 12% ~ 20% of the rated voltage. When motor runs in the higher voltage,
the temperature of motor will be risen, the insulation will be destroyed and the output of
torque will be unsteadily. The motor will be short life if using in these situation for a long
time.
This function will make the output power stay on the rated voltage of motor when input
power exceeds the rated voltage of motor. For example, V/F curve is set to AC
200V/50Hz, input power is AC 200 ~ 264V, the voltage that output to motor will be AC
200V/50Hz and not exceed the setting voltage. If the input power vary between AC 180
~ 200V, the voltage that output to motor will be the same ratio with input power.
Selecting program value 2 enables the AVR function and will disables the AVR function
during deceleration. This offers a quicker deceleration.
08 - 17
Software Setting of the Braking Level
(the Action Level of the Braking Resistor)
Unit: 1
Settings 230V series: 370 to 430V Factory Setting: 380
460V series: 740 to 860V Factory Setting: 760