Delta DVP-ES2 User Manual Page 92

  • Download
  • Add to my manuals
  • Print
  • Page
    / 702
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 91
DVP-ES2/EX2/SS2/SA2/SX2/SE Operation Manual - Programming
Communication Error Code
Function Group
M1025, D1025
Number
Contents:
In the connection between PLC and PC/HMI, M1025 will be ON when PLC receives illegal
communication request during the data transmission process. The error code will be stored in
D1025.
01: illegal instruction code
02: illegal device address.
03: requested data exceeds the range.
07: checksum error
Pulse output Mark and Mask function
Function Group
M1108, M1110, M1156, M1158, M1538, M1540, D1026, D1027, D1135, D1136,
D1232, D1233, D1234, D1235, D1348, D1349
Number
Contents:
Please refer to explanations of API 59 PLSR / API 158 DDRVI / API 197 DCLLM instructions.
Execution Completed Flag
Function Group
M1029, M1030, M1102, M1103
Number
Contents:
Execution Completed Flag:
MTR, HKY, DSW, SEGL, PR:
M1029 = ON for a scan cycle whenever the above instructions complete the execution.
PLSY, PLSR:
1. M1029 = ON when Y0 pulse output completes.
2. M1030 = ON when Y1 pulse output completes
3. M1102 = ON when Y2 pulse output completes.
4. M1103 = ON when Y3 pulse output completes.
5. When PLSY, PLSR instruction are OFF, M1029, M1030, M1102, M1103 will be OFF as well.
When pulse output instructions executes again, M1029, M1030, M1102, M1103 will be OFF
and turn ON when execution completes.
6. Users have to clear M1029 and M1030 manually.
INCD
:
M1029 will be “ON” for a scan period when the assigned groups of data comparison is completed
RAMP, SORT:
1. M1029= ON when instruction is completed. M1029 must be cleared by user manually.
2. If this instruction is OFF, M1029 will be OFF.
2-60
Page view 91
1 2 ... 87 88 89 90 91 92 93 94 95 96 97 ... 701 702

Comments to this Manuals