June 2005
CAT.02.02.S.K.CD For more information visit: www.EatonElectrical.ca
9
XT IEC Power Control
Relays and Timers
Technical Data and Specifications
Technical Data and Specifications
Table 12. Relays and Timers — Technical Data and Specifications
Description XTRE XTCEXFAC_ XTRM XTMCXFA_
General
Standards IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, Mechanical
AC Operated
DC Operated
20,000,000
20,000,000
10,000,000
10,000,000
10,000,000
20,000,000
10,000,000
20,000,000
Maximum operating frequency (ops/hr) 9000 9000 9000 9000
Climatic Proofing Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclical, to IEC 60068-2-30
Ambient Temperature
Open (°C)
Enclosed (°C)
Ambient Temperature for Storage (°C)
-25/60
-25/40
-40/80
-25/60
-25/40
-40/80
-25/50
-25/40
—
-25/50
-25/40
—
Mounting Position As required, except vertically A1/A2 at
the bottom
Mechanical shock resistance (IEC/EN 60068-2-27)
Half-sinusoidal shock 10 ms
Base unit with auxiliary contact module
Make contact
Break contact
Half-sinusoidal shock 20 ms
Base unit with auxiliary contact module
Make contact
Break contact
7g
5g
—
—
—
—
—
—
10g
8g
—
—
10g
8g
—
—
Degree of Protection IP20 IP20 IP20 IP20
Protection against direct contact from the front when actuated by a perpen-
dicular test finger (IEC 536)
Finger- and back-of-hand proof
Weight
AC operated (kg)
DC operated (kg)
0.23
0.28
0.23
0.28
0.17
0.20
—
—
Terminal capacity
Screw terminals
Solid (mm
2
)
Flexible with ferrule (mm
2
)
Solid or stranded (AWG)
1 x (0.75 – 4)
2 x (0.75 – 2.5)
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
18 – 14
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
1 x (0.75 – 1.5)
2 x (0.75 – 1.5)
18 – 14
Terminal screw M3.5 M3.5 M3.5 M3.5
Pozidriv screwdriver Size 2 Size 2 Size 2 Size 2
Standard screwdriver (mm) 0.8 x 5.5
1 x 6
0.8 x 5.5
1 x 6
Max. tightening torque (Nm) 1.2 1.2 1.2 1.2
Spring cage terminals
Solid (mm
2
)
Flexible with or without ferrule DIN 46228 (mm
2
)
Solid or stranded (AWG)
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
18 – 14
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
18 – 14
Standard screwdriver (mm) 0.6 x 3.5
Contacts
Interlocked opposing contacts to ZH 1/457,
including auxiliary contact module
——YesYes
Rated impulse withstand voltage (U
imp
) V AC 6000 6000 6000 6000
Overvoltage category/pollution degree III/3 III/3 III/3 III/3
Rated insulation voltage (U
i
) V AC 690 690 690 690
Rated operational voltage (U
e
) V AC 690 500 600 600
Safe isolation to VDE 0106 Part 101 and Part 101/A1
Between coil and auxiliary contacts (V AC)
Between the auxiliary contacts (V AC)
400
400
400
400
300
300
300
300
Rated operational current
AC-15 220/240V I
e
380/415V Ie
500V I
e
6
4
1.5
6
3
—
6
3
1.5
4
2
1.5
180°
30°
90°90°90°