Delta Three Phase 1342457 06-03-05 Service Manual Page 145

  • Download
  • Add to my manuals
  • Print
  • Page
    / 188
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 144
June 2005
CAT.02.02.S.K.CD For more information visit: www.EatonElectrical.ca
143
XT IEC Power Control
Manual Motor Protectors
Technical Data and Specifications
Table 201. XT Manual Motor Protectors — Technical Data and Specifications (Continued)
Table 202. Auxiliary Contacts — Technical Data and Specifications
XTPBP16B –
XTPB016B
XTPRP16B –
XTPR032B
XTPR016D –
XTPR063D
XTPMP16B –
XTPM032B
XTPTP16B –
XTPT025B
Main Contacts (Continued)
Short-circuit rating
AC See Page 137.
DC (kA) 60 60 (up to
XTPR016B)
40 (XTPR020B –
XTPR032B)
60 60 (up to
XTPM016B)
40 (XTPM020B –
XTPR032B)
60 (up to
XTPT016B)
40 (XTPT020B –
XTPT025B)
Motor switching capacity
AC-3 (up to 690 V) in amperes
DC-5 (up to 250 V) in amperes
16
16
32
25 (3 contacts in
series)
63
63 (3 contacts in
series)
32 25
Overload release setting range (x I
u
) 0.6 – 1.0 0.6 – 1.0 0.6 – 1.0 0.6 – 1.0
Fixed short-circuit release (x I
u
)1414141414
Short-circuit release tolerance ± 20% ± 20% ± 20% ± 20% ± 20%
Phase-failure sensitivity IEC/EN 60947-1-1, VDE 0660 Part 102 IEC/EN 60947-1-1,
VDE 0660 Part 102
Description XTPAXSA_ _ XTPAXFA_ _ XTPAXCMSA_ _ XTPA(B)XFAEM_ _ XTPAXSATR_ _
Rated Impulse withstand voltage, U
imp
(V AC) 6000 4000 6000 4000 6000
Overvoltage category/pollution degree III/3 III/3 III/3 III/3 III/3
Rated operational voltage
U
e
(VAC)
U
e
(VDC)
500
250
440
250
500
250
440
250
500
250
Safe isolation to VDE 0106 Part 101 and Part 101/A1
Between auxiliary contacts and main contacts (V AC) 690 690 690 690 690
Rated operational current
AC-15
220 – 240 V, I
e
(A)
380 – 415 V, I
e
(A)
440 – 500 V, I
e
(A)
3.5
2
1
1
3.5
2
1
1
3.5
2
1
DC-13 L/R < 100 ms
24 V, I
e
(A)
60 V, I
e
(A)
110 V, I
e
(A)
220 V, I
e
(A)
2
1.5
1
0.25
2
1.5
1
0.25
2
1.5
1
0.25
Lifespan
Mechanical, operations (x 10
6
)> 0.1 > 0.1 > 5 > 0.1 > 0.01
Electrical, operations (x 10
6
)> 0.05 > 0.1 > 1 > 0.1 > 0.005
Contact reliability (@ U
e
= 24V DC, U
min
– 17V,
I
min
= 5.4 mA, fault probability (λ)
< 10
-8
< 1 fault at 1 x 10
8
operations
Positively driven contacts to ZH 1/457 Yes Yes
Short-circuit rating without welding
Fuseless FAZ-B4/1-HI FAZ-B4/1-HI FAZ-B4/1-HI
Fuse (A gG/gL) 10 10 10 10 10
Terminal Capacity
Solid or flexible conductor with ferrule (mm
2
) 0.75 –2.5 0.75 – 1.5 0.75 – 2.5 0.75 – 1.5 0.75 – 2.5
Solid or stranded (AWG) 18 – 14 18 – 16 18 – 14 18 – 16 18 – 14
Page view 144
1 2 ... 140 141 142 143 144 145 146 147 148 149 150 ... 187 188

Comments to this Manuals