June 2005
70
For more information visit: www.EatonElectrical.ca CAT.02.02.S.K.CD
XT IEC Power Control
Contactors, Starters and Overload Relays
Technical Data and Specifications
AC Ratings
Table 109. AC Ratings
At maximum permissible ambient temperature.
Example —
The transformer has a nominal current of 10A with an inrush current of 18 times the nominal current. So, the contactor must have an AC-3 current of
18/6 x 10A = 30A. Using an XTCE032C (32A AC-3) contactor is recommended.
Description XTCE007B XTCE009B XTCE012B XTCE015B XTCE018C XTCE025C XTCE032C
AC-1 Operation
Conventional Free Air Thermal Current,
3-Pole, 50 – 60 Hz
at 40°C (I
th
)
at 50°C (I
th
)
at 55°C (I
th
)
at 60°C (I
th
)
22A
21A
21A
20A
22A
21A
21A
20A
22A
21A
21A
20A
22A
21A
21A
20A
40A
38A
37A
35A
45A
43A
42A
40A
45A
43A
42A
40A
Conventional Free Air Thermal Current,
1-Pole (I
th
)
50A 50A 50A 50A 85A 85A 85A
AC-3 Operation
Rated Operational Current, 50/60 Hz
(I
e
)
in amperes
220/230V
240V
380/400V
415V
440V
500V
660/690V
1000V
7
7
7
7
7
5
4
9
9
9
9
9
7
5
12
12
12
12
12
10
7
15.5
15.5
15.5
15.5
15.5
12.5
9
18
18
18
18
18
18
12
25
25
25
25
25
25
15
32
32
32
32
32
32
18
Rated power (P) in kilowatts
220/230V
240V
380/400V
415V
440V
500V
660/690V
1000V
2.2
2.2
3
4
4.5
3.5
3.5
2.5
3
4
5.5
5.5
4.5
4.5
3.5
4
5.5
7
7.5
7
6.5
4
4.6
7.5
8
8.4
7.5
7
5
5.5
7.5
10
10.5
12
11
7.5
8.5
11
14.5
15.5
17.5
14
10
11
15
19
20
23
17
AC-4 Operation
Rated Operational Current, 50/60 Hz
(I
e
)
in amperes
220/230V
240V
380/400V
415V
440V
500V
660/690V
1000V
5
5
5
5
5
4.5
4
6
6
6
6
6
5
4.5
7
7
7
7
7
6
5
7
7
7
7
7
6
5
10
10
10
10
10
10
8
13
13
13
13
13
13
10
15
15
15
15
15
15
12
Rated power (P) in kilowatts
220/230V
240V
380/400V
415V
440V
500V
660/690V
1000V
1
1.5
2.2
2.3
2.4
2.5
2.9
1.5
1.6
2.5
2.8
3
2.8
3.6
2
2.2
3
3.4
3.6
3.5
4.4
2
2.2
3
3.4
3.6
3.5
4.4
2.5
3
4.5
5
5.5
6
6.5
3.5
4
6
6.5
7
8
8.5
4
4.5
7
7.5
8
9
10
AC-6A Operation
Transformer Loads Values are application specific. Calculation is I
e
AC-3
= X / 6 * I
e Transformer where X is the inrush current of the
transformer and
I
e Transformer is the nominal current.
AC-6B Operation
Capacitor Loads
Individual compensation rated operational cur-
rent I
e
of three-phase capacitors in amperes
Up to 525V
690V
Maximum inrush current peak (x I
e
)— — — — — —
Component Lifesaving (Operations) — — — — — — —
Maximum Operating Frequency (ops/hr) — — — — — — —