XT IEC Power Control
Contactors, Starters and Overload Relays
Technical Data and Specifications
Table 106. Coil Data — Frames L – R (Continued)
Control transformer with U
k
7%.
Description XTCE580N XTCE750N, XTCE820N XTCEC10N XTCEC14P XTCEC20R
Voltage Tolerance
Pick-Up (x U
c
)
XTCE185L – XTCEC20R
XTCS185L – XTCS500M
Drop-Out (x U
c
)
XTCE185L – XTCEC20R
XTCS185L – XTCS500M
0.7 x U
cmin
— 1.15 x U
cmax
0.85 x U
cmin
— 1.1 x U
cmax
0.2 x U
cmin
— 0.6 x U
cmax
0.2 x U
cmin
— 0.4 x U
cmax
Power Consumption of the coil at cold state and 1.0 x U
c
XTCE185L – XTCEC20R
Pick-Up VA
Pick-Up W
Sealing VA
Sealing W
800
700
7.5
6.5
800
700
7.5
6.5
800
700
7.5
6.5
800
700
7.5
6.5
1600
1400
15
13
XTCS185L -– XTCS500M
Pick-Up VA
Pick-Up W
Sealing VA
Sealing W
Duty Factor (%DF) 100 100 100 100 100
Switching Time at 100% Main Contact U
c
(approximate values)
XTCE185L – XTCEC20R
Closing delay (mS)
Opening delay (mS)
XTCS185L – XTCS500M
Closing delay (mS)
Opening delay (mS)
<70
<70
<70
<70
<70
<70
<70
<40
<70
<40
Reaction in Threshold and Sealing State Transition Range (XTCE185L – XTCEC20R)
Voltage interruptions
(0 – 0.2 x U
cmin
) 10ms
(0 – 0.2 x U
cmin
) > 10ms
Time is bridged successfully
Drop-out of the contactor
Voltage Dips
(0.2 – 0.6 x U
cmin
) 12ms
(0.2 – 0.6 x U
cmin
) > 12ms
(0.6 – 0.7 x U
cmin
)
Time is bridged successfully
Drop-out of the contactor
Contactor remains switched on
Excess Voltage
(1.15 – 1.3 x U
cmax
)
(>1.3 x U
cmax
) 3s
(>1.3 x U
cmax
) > 3s
Contactor remains switched on
Contactor remains switched on
Drop-out of the contactor
Pick – Up phase
(0 – 0.7 x U
cmin
)
(0.7 x U
cmin
–1.15 x U
cmax
)
(>1.15 x U
cmax
)
Contactor does not switch on
Contactor switches on with certainty
Contactor switches on with certainty
Permissible contact resistance (of the external
command device with actuation of A11),
500 500 500 500 500
Permissible residual current (with actuation of
A11 by the electronics with 0 signal)
1 1 1 1 1
SPS Signal Level (A3 – A4) to
IEC/EN 61131-2 (Type 2)
High
Low
15V
5V
15V
5V
15V
5V
15V
5V
15V
5V
Electromagnetic compatibility (EMC) This product is designed for operation in industrial environments. Usage in domestic areas can cause radio