June 2005
56
For more information visit: www.EatonElectrical.ca CAT.02.02.S.K.CD
XT IEC Power Control
Contactors, Starters and Overload Relays
Technical Data and Specifications
Frame C – D
Table 99. XT Contactors Technical Data and Specifications — Frame C – D
Description XTCE018C XTCE025C XTCE032C XTCE040D XTCE050D XTCE065D
General
Standards IEC/EN 60947, VDE 0660, UL, CSA, CCC, RoHS
Weights in kg [Lb]
AC operated
DC operated
0.42 [0.93]
0.48 [1.06]
0.42 [0.93]
0.48 [1.06]
0.42 [0.93]
0.48 [1.06]
0.9 [2.0]
1.1 [2.4]
0.9 [2.0]
1.1 [2.4]
0.9 [2.0]
1.1 [2.4]
Mechanical Life 10,000,000 10,000,000 10,000,000 10,000,000 10,000,000 10,000,000
Mechanical Operating Frequency (ops/hr)
AC operated
DC operated
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
Mechanical Operating Frequency (ops/hr)
AC-1; 400V I
e
AC-3; 400V I
e
AC-4; 400V I
e
800
800
300
800
800
300
800
800
300
800
800
300
800
800
300
800
800
300
Climatic Proofing Damp heat, constant, to IEC 60068-2-78;
Damp heat, cyclic, to IEC 60 068-2-30
Insulation Voltage (U
i
) VAC 690 690 690 690 690 690
Impulse Withstand Voltage (U
imp
) VAC 8000 8000 8000 8000 8000 8000
Operating Voltage (U
e
) VAC 690 690 690 690 690 690
Safe Isolation to VDE 0106 Part 101 and Part 101/A1
Between coil and contacts (VAC)
Between contacts (VAC)
440
238
440
440
440
440
440
440
440
440
440
440
Making Capacity (Amps) 238 350 384 560 700 910
Breaking Capacity (Amps)
220/230V
380/400V
500V
660/690V
170
170
170
120
250
250
250
150
320
250
250
150
400
400
400
250
500
500
500
320
650
650
650
370
Short-Circuit Protection Rating Maximum Fuse
Type 2 Coordination
400V; gG/gL 500V
690V; gG/gL 690V
Type 1 Coordination
400V; gG/gL 500V
690V; gG/gL 690V
25
25
63
50
35
35
100
50
63
35
125
63
63
50
125
80
80
63
160
80
125
80
250
100
Degree of Protection IP00
Protection against Direct Contact when
Actuated from Front (IEC 536)
Finger- and back-of-hand proof
Main Cable Cross-Section
Solid (mm
2
)1 x (0.75 – 16)
2 x (0.75 – 10)
1 x (0.75 – 16)
2 x (0.75 – 10)
1 x (0.75 – 16)
2 x (0.75 – 10)
1 x (0.75 – 16)
2 x (0.75 – 10)
1 x (0.75 – 16)
2 x (0.75 – 10)
1 x (0.75 – 16)
2 x (0.75 – 10)
Flexible with ferrule (mm
2
)1 x (0.75 – 16)
2 x (0.75 – 10)
1 x (0.75 – 16)
2 x (0.75 – 10)
1 x (0.75 – 16)
2 x (0.75 – 10)
1 x (0.75 – 16)
2 x (0.75 – 10)
1 x (0.75 – 16)
2 x (0.75 – 10)
1 x (0.75 – 16)
2 x (0.75 – 10)
Solid or Stranded (AWG) 18 – 6 18 – 6 18 – 6 18 – 6 18 – 6 18 – 6
Flat Conductor
(Number of Segments x Width x Thickness)
———
2 x (6 x 9 x 0.8) 2 x (6 x 9 x 0.8) 2 x (6 x 9 x 0.8)
Main Cable Connection Screw/Bolt
Tightening torque
Nm
Lb-in
M5
3
26.6
M5
3
26.6
M5
3
26.6
M6
3
26.6
M6
3
26.6
M6
3
26.6
Control Circuit Cable Cross-Sections
Solid (mm
2
)1 x (0.75 – 4)
1 x (0.75 – 4)
1 x (0.75 – 4)
1 x (0.75 – 4)
1 x (0.75 – 4)
1 x (0.75 – 4)
1 x (0.75 – 4)
1 x (0.75 – 4)
1 x (0.75 – 4)
1 x (0.75 – 4)
1 x (0.75 – 4)
1 x (0.75 – 4)
Flexible with ferrule (mm
2
)1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
Solid or Stranded (AWG) 18 – 14 18 – 14 18 – 14 18 – 14 18 – 14 18 – 14
Control Circuit Cable Connection Screw/Bolt
Tightening torque
Nm
Lb-in
M3.5
1.2
10.6
M3.5
1.2
10.6
M3.5
1.2
10.6
M3.5
1.2
10.6
M3.5
1.2
10.6
M3.5
1.2
10.6
Tools
Main and control circuit cable
Pozidrive screwdriver
Standard screwdriver
Size 2
0.8 x 5.5
1 x 6
Size 2
0.8 x 5.5
1 x 6
Size 2
0.8 x 5.5
1 x 6
Size 2
0.8 x 5.5
1 x 6
Size 2
0.8 x 5.5
1 x 6
Size 2
0.8 x 5.5
1 x 6
Comments to this Manuals