XT IEC Power Control
Miniature Controls
Technical Data and Specifications
Technical Data and Specifications
Table 36. XT Miniature Controls — General Specifications
Description XTMC6A… XTMC9A… XTMF9A…
Coils A – Y Coils AD – WD Coils A – Y Coils AD – WD Coils A – Y Coils AD – WD
Physical and Electrical
Standards IEC/EN 60947, VDE 0660, CSA, UL, CCC
Weights in kg [lb] 0.2 [0.44] 0.17 [0.37] 0.2 [0.44] 0.17 [0.34] 0.2 [0.44] 0.17 [0.37]
Mechanical Life — Operations 10,000,000 20,000,000 10,000,000 20,000,000 20,000,000
Mechanical Life — Coil @ 50 Hz 7 7 7
Maximum mechanical operating frequency (ops/hr) 9000
Insulation Voltage (U
i
) VAC 690 690 690 690 690 690
Impulse Withstand Voltage (U
imp
) VAC 6000 6000 6000 6000 6000 6000
Operational Voltage (U
e
) VAC 690 690 690 690 690 690
Safe Isolation to VDE 0106 Part 101 and Part 101/A1
between coil and contacts (VAC)
between contacts (VAC)
300
300
300
300
300
300
300
300
300
300
300
300
Making Capacity (amps) 110 110 110 110 110 110
Breaking Capacity (amps)
220/230V
380/400V
500V
660/690V
90
90
64
54
90
90
64
54
90
90
64
54
90
90
64
54
90
90
64
54
90
90
64
54
Short-Circuit Protection rating maximum fuse (gL/gG)
Type 2 Coordination (A)
Type 1 Coordination (A)
10
20
10
20
10
20
10
20
10
20
10
20
Degree of Protection IP20
Protection against direct contact when actuated from
front (IEC 536)
Finger- and back-of-hand proof
Terminal Capacity of main and auxiliary contacts
Solid (mm
2
)1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
1 x (0.75 – 2.5)
2 x (0.75 – 2.5
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
Flexible with ferrule (mm
2
)1 x (0.75 – 1.5)
2 x (0.75 – 1.5)
1 x (0.75 – 1.5)
2 x (0.75 – 1.5)
1 x (0.75 – 1.5)
2 x (0.75 – 1.5)
1 x (0.75 – 1.5)
2 x (0.75 – 1.5)
1 x (0.75 – 1.5)
2 x (0.75 – 1.5)
1 x (0.75 – 1.5)
2 x (0.75 – 1.5)
Solid or Stranded (AWG) 18-14 18-14 18-14 18-14 18-14 18-14
Terminal Screw M3.5 M3.5 M3.5 M3.5 M3.5 M3.5
Posidrive screwdriver Size 2 Size 2 Size 2 Size 2 Size 2 Size 2
Standard screwdriver (mm) 0.8 x 5.5
1 x 6
0.8 x 5.5
1 x 6
0.8 x 5.5
1 x 6
0.8 x 5.5
1 x 6
0.8 x 5.5
1 x 6
0.8 x 5.5
1 x 6
Max. Tightening Torque
Nm
Lb-in
1.2
10.6
1.2
10.6
1.2
10.6
1.2
10.6
1.2
10.6
1.2
10.6
Terminal Capacity of spring cage main terminals
Solid (mm
2
)1 x (1 – 2.5)
2 x (1 – 2.5)
1 x (1 – 2.5)
2 x (1 – 2.5)
1 x (1 – 2.5)
2 x (1 – 2.5)
1 x (1 – 2.5)
2 x (1 – 2.5)
1 x (1 – 2.5)
2 x (1 – 2.5)
1 x (1 – 2.5)
2 x (1 – 2.5)
Flexible with ferrule (mm
2
)1 x (1 – 2.5)
2 x (1 – 2.5)
1 x (1 – 2.5)
2 x (1 – 2.5)
1 x (1 – 2.5)
2 x (1 – 2.5)
1 x (1 – 2.5)
2 x (1 – 2.5)
1 x (1 – 2.5)
2 x (1 – 2.5)
1 x (1 – 2.5)
2 x (1 – 2.5)
Standard screwdriver (mm) 0.6 x 3.5 0.6 x 3.5 0.6 x 3.5 0.6 x 3.5 0.6 x 3.5 0.6 x 3.5
Mounting Position As required, except vertical with terminals A1/A2 at the bottom
Environmental
Ambient Temperature -25° to 50°C [-13° to 122°F]
Mechanical Shock Resistance (IEC/EN 60068-2-27)
Half-sinusoidal shock 10 ms
Contactor without auxiliary contact module
Main contact — make contact
Main contact — break/make contact
Contactor with auxiliary contact module
Main contact — make contact
Main contact — make/break contact
10g
10/8g
10g
20/20g
10g
10/8g
10g
20/20g
10g
10/8g
10g
20/20g
10g
10/8g
10g
20/20g
10g
10g
20/20g
10g
10g
20/20g
Climatic Proofing Damp heat, constant, to IEC 60 068-2-78; Damp heat, cyclic, to IEC 60 068-2-30
Pollution Degree III/3 III/3 III/3 III/3 III/3 III/3
A2
A1
Page view 22