XT IEC Power Control
Contactors, Starters and Overload Relays
Technical Data and Specifications
Overload Relays
These tripping characteristics are the
mean values of the spread at 20°C
ambient temperature in a cold state.
Tripping time depends on response
current. With devices at operating tem-
perature, the tripping time of the over-
load relay reduces to approximately
25% of the read off value. Specific
characteristics for each individual set-
ting range can be found in
MN03402001E.
Figure 36. Tripping Characteristics
Table 107. Overload Relay — Technical Data and Specifications
Ambient temperature operating range to IEC/EN 60947, PTB: -5°C to +50°C.
6 mm
2
flexible with ferrules to DIN 46228.
Main contact terminal capacity, solid and stranded conductors with ferrules: When using 2 conductors use identical cross-section.
2h
100
60
40
20
10
6
4
2
1
40
20
10
6
4
2
1
0.6
XTOB...BC1,
XTOB...CC1,
XTOB...DC1
1 1.5 2 3 4 68 10 15 20
x Setting Current
2-Phase
Seconds
Minutes
3-Phase
Description XTOB…BC1, XTOB…CC1 XTOB…DC1
General
Standards IEC/EN 60947, VDE 0660, UL, CSA IEC/EN 60947, VDE 0660, UL, CSA
Climatic Proofing Damp heat, constant, to IEC 60068-2-78;
Damp heat, cyclic, to IEC 60 068-2-30
Damp heat, constant, to IEC 60068-2-78;
Damp heat, cyclic, to IEC 60 068-2-30
Ambient Temperature
-25 to 50°C [-13 to 122°F] -25 to 50°C [-13 to 122°F]
Temperature Compensation Continuous Continuous
Mechanical Shock Resistance (IEC/EN 60068-2-27)
Half-sinusoidal Shock 10 mS 10g 10g
Degree of Protection IP20 IP20
Protection against Direct Contact when Actuated
from Front (IEC 536)
Finger and back of hand proof Finger and back of hand proof
Insulation Voltage (U
i
) VAC 690 690
Overvoltage Category /Pollution Degree III/3 III/3
Impulse Withstand Voltage (U
imp
) VAC 6000 6000
Operational Voltage (U
e
) VAC 690 690
Safe Isolation to VDE 0106 Part 101 and Part 101/A1
Between auxiliary contacts and main contacts (VAC)
Between main contacts (VAC)
440
440
440
440
Overload Relay Setting Range 0.1 – 32A 6 – 75A
Temperature Compensation Residual Error >20°C (%/K) 0.25 0.25
Current Heat Loss (3 Conductors)
Lower value of setting range, W
Upper value of setting range, W
2.5
6
3
7.5
Terminal Capacity
Solid, mm
2
Flexible with ferrule, mm
2
2 x (1 – 6)
2 x (1 – 4)
2 x (1 – 6)
2 x (1 – 16)
1 x 25
2 x (1 – 10)
Solid or Stranded, AWG 14-8 14-2
Terminal Screw
Tightening Torque
Nm
Lb-in
M4
1.8
16
M6
3.5
31
Tools
Pozidrive screwdriver
Standard screwdriver
Size 2
1 x 6
Size 2
1 x 6
Page view 68