Delta 1.07 VFD-D D User Manual Page 61

  • Download
  • Add to my manuals
  • Print
  • Page
    / 141
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 60
Chapter 4 Parameter Settings|DD Series
4-37
Settings 0.00~120.00Hz
Output Voltage 3
Control mode
VF
VFPG
Factory setting: 5.0
Settings 0.0V~240.0V
Output Frequency 4
Control mode
VF
VFPG SVC FOCPG
Factory setting: 0.00
Settings 0.00~120.00Hz
Output Voltage 4
Control mode VF
VFPG
Factory setting: 0.0
Settings 0.0V~240.0V
V/f curve setting is usually set by the motor’s allowable loading characteristics. Pay special attention to
the motor’s heat dissipation, dynamic balance, and bearing lubricity, if the loading characteristics exceed
the loading limit of the motor.
The frequency setting of V/F curve must be set according to this rule, Pr. 01.3201.3401.3601.38.
There is no limit for the voltage setting, but a high voltage at low frequency may cause motor damage,
overheat, and stall prevention or over-current protection. Therefore, please use the low voltage at the low
frequency to prevent motor damage.
01.36
01.34 01.32
01.31
Voltage
Frequency
Max. Output
Frequency
Output Voltage 1
0 1.33
V/F Curve
Output
Frequency
2
01.38
Fre quency Ou tput
Limit
Output Voltage 2
0 1.35
Output Voltage 3
0 1.37
Output Voltage 4
0 1.39
Output
Frequency
1
Output
Fre quen cy
3
Output
Frequency
4
Page view 60
1 2 ... 56 57 58 59 60 61 62 63 64 65 66 ... 140 141

Comments to this Manuals

No comments