Chapter 4 Parameter Settings|DD Series
4-20
09 Communication Parameters This parameter can be set during operation.
Paramete
r
Explanation Settings
Factory
Setting
VF
VFP
SVC
FOC
FOC
09.00
Communication Address
01~254 1
09.01
Transmission Speed
4.8115.2Kbps
19.2
09.02
Transmission Fault
Treatment
0: Warn and keep operation
1: Warn and ramp to stop
2: Reserved
3: No action and no display
3
09.03
Time-out Detection
0.0100.0sec
0.0
09.04
Communication Protocol
0: 7N1 (ASCII)
1: 7N2 (ASCII)
2: 7E1 (ASCII)
3: 7O1 (ASCII)
4: 7E2 (ASCII)
5: 7O2 (ASCII)
6: 8N1 (ASCII)
7: 8N2 (ASCII)
8: 8E1 (ASCII)
9: 8O1 (ASCII)
10: 8E2 (ASCII)
11: 8O2 (ASCII)
12: 8N1 (RTU)
13: 8N2 (RTU)
14: 8E1 (RTU)
15: 8O1 (RTU)
16: 8E2 (RTU)
17: 8O2 (RTU)
13
09.05
Response Delay Time
0.0~200.0ms 2.0