6–16 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
CONFIGURATION SETPOINTS CHAPTER 6: SETPOINTS
The terminal designation is indicated under the “Terminal” column. The values in the first
column are determined from the installed option cards and cannot be edited.
When a starter type is selected, the first equipped contact output and the first equipped
contact input are forced to the contactor A relay function and the contactor A status
function, respectively. When the two-speed or reversing starter type is selected, the
second equipped contact output and the second equipped contact input are forced to the
contactor B relay function and the contactor B status function, respectively. Any prior
values for these setpoints are erased, and the setpoint becomes non-editable.
For contact outputs the Function setpoint determines which internal signal turns the
output on and off. A list of the setpoints options with descriptions is shown below. For
more information on a particular option, see the appropriate section in this manual.
"Contactor A Relay": This value represents an output contact that energizes contactor
A. It is used by the starters, the stop/start control element, and the system trouble
function, and automatically assigned to the first output when a starter type is
selected. Not otherwise user assignable.
"Contactor B Relay": This value represents an output contact that energizes contactor
B. It is used by the starters, the stop/start control element, and the system trouble
function, and automatically assigned to the second output when a reversing, two-
speed, inverter, or soft starter type is selected, and when the custom starter is
selected and uses this output. Not otherwise user assignable.
FlexLogic™ operands: Any FlexLogic™ operand can be assigned to a contact output.
Select Home > Setpnts > CFG > Outputs > Trips to edit the Trips setpoints:
Figure 13: Output configuration setpoints trips page
Comm Trip
Range: N/A, C2, D1... D4 (order code dependent)
Default: N/A
This setting assigns the Comm Trip Available element to the desired contact output.
Select Home > Setpnts > CFG > Outputs > Ctrl to edit the Control setpoints: