6–4 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
CONFIGURATION SETPOINTS CHAPTER 6: SETPOINTS
Motor Name
Range: up to 20 alphanumeric characters
Default: Motor Name
This setpoint specifies a name for the motor. This name will appear in the actual values,
sequence of events record, and other reports.
Starter Type (Mandatory Setpoint)
Range: None, FV Non-Reversing, FV Reversing, Two Speed, Wye-Delta, Inverter, Soft
Starter, Custom Starter
Default: FV Non-Reversing
This setpoint selects the starter type. The relay is essentially disabled when the value is
set to “None”. The following figure illustrates typical starter timing beginning from the
stopped state for all starter types.
Motor FLA (Mandatory Setpoint)
Range: 0.5 to 1000.0 amps in steps of 0.1
Default: OFF
This setpoint must be specified for motor protection. The value may be taken from the
motor nameplate data sheets.
Motor Nameplate Voltage (Mandatory Setpoint)
Range: 100 to 690 volts in steps of 1
Default: 690 volts
This setpoint specifies the rated motor nameplate voltage. This value represents the
base phase-to-phase voltage, and is used by the undervoltage and overvoltage
protection elements.
Supply Frequency (Mandatory Setpoint)
Range: 50 Hz, 60 Hz
Default: 60 Hz
This setpoint specifies the nominal system frequency.
Motor Rating (Mandatory Setpoint)
Range: 0.3 to 1100.0 kW in steps of 0.1 or OFF
Default: OFF
This setpoint specifies the motor rating (or low speed motor rating for two-speed
starters) in kWs.