2–18 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
ELECTRICAL INSTALLATION CHAPTER 2: INSTALLATION
2.2.4.1 Type IO_C module connections
Figure 22: Typical wiring for type IO_C module
The IO_C module contains two form-A contact output relays, six digital inputs and control
voltage input.
Contact inputs can be programmed to any of the input functions, such as field stop or
process interlock. The exception is that contactor A status is fixed as the first contact
input, and contactor B status (where used) is fixed as the second contact input.
An AC auxiliary supply must be connected to terminals 12 and 13. This auxiliary voltage
(from slot C only) is also used for actual value indication, for auxiliary undervoltage, and for
undervoltage restart. When three-phase voltages are not available, it is also used to
calculate power quantities and is used as a phase angle reference.
When the I0_C module senses an interruption to its auxiliary supply, it raises an AC Low
Aux Voltage Inhibit, and freezes the last valid state of the contact inputs, as the
interruption prevents sensing the actual states.
The two contact outputs can be programmed to follow any one of the digital signals
developed by the MM300, such as alarms and status signals. The exception is that the
contactor A relay is fixed as the first contact output, and contactor B relay is fixed as the
second contact output (where used).
NOTE
NOTE:
Connect AUX VT to the Control Supply for correct operation of the UV Restart feature and
readings of inputs.
NOTE
NOTE:
All IO_C cards must have the auxiliary input VT wired for proper input sensing.
NOTE
NOTE:
Substitute the slot position of the input/output module (C E, F, G, H) wherever the tilde
symbol “~” appears in the diagrams above.
Contactors
~1
~2
~4
~3
853741A3.CDR
~5
~6
MM300
Motor Management System
~8
~9
~11
~10
~12
~13
~7
~14
Two form-A
contact outputs
CONTACT OUTPUT 2
CONTACT INPUT 1 +
Six contact
(digital) inputs
CONTACT OUTPUT 1
CONTACT INPUT 2 +
CONTACT INPUT 3 +
CONTACT INPUT 4 +
CONTACT INPUT 5 +
CONTACT INPUT 6 +
COMMON
VT INPUT
SURGE
L
N
AC
Control power
+
B
A
A
B