6–22 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
CONFIGURATION SETPOINTS CHAPTER 6: SETPOINTS
Phasor Display
Range: Leading, Lagging
Default: Lagging
The customer has the choice to display either lagging or leading phasor quantities.
6.2.7 Events
Figure 18: Events setpoint page
The following setpoints are available.
Event Recorder Function
Range: Enabled, Disabled
Default: Enabled
Enables or disables the Event Recorder feature.
Recording of Trip Events
Range: Enabled, Disabled
Default: Enabled
Enables or disables the recording of Trip events.
Recording of Alarm Events
Range: Enabled, Disabled
Default: Enabled
Enables or disables the recording of Alarm events.
Recording of Control Events
Range: Disabled, Enabled
Default: Enabled
Enables or disables the recording of Control events.
Recording of Set Time/Date Events
Range: Disabled, Enabled
Default: Disabled
Enables or disables the recording of Time and Date storage events.