6–32 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
PROTECTION ELEMENTS CHAPTER 6: SETPOINTS
Figure 25: Thermal model cooling following a trip at t =0
6.3.1.6 Thermal protection reset
Operating at the thermal model protection limit is a serious event, and results in a lockout
that can not be reset until the motor has cooled, except with a level 2 or level 3 security
login. A setpoint is available (Minimize Reset Time - see section 6.3.1) that controls whether
lockout persists until the motor has cooled until the thermal capacity used reaches 15%
(approximately twice the cool time stopped setpoint), or until the relay estimates based on
learned thermal capacity used on start that the motor has cooled sufficiently for a
successful restart. For the latter, a 2% safety margin is included. While in lockout, the
motor can not be started via the MM300. Refer to section 6.4.2 - Thermal Start Inhibit, for
details.
If the motor is re-started it may re-trip quickly. Should process interruption concerns
outweigh the probable damage to the motor that early starting would incur, an external
circuit should be added that bypasses the relay to directly close the motor contactor.
A second setpoint controls whether once the motor has cooled as described above, the
lockout is replaced with a trip that can be manually reset without security login, or
alternatively the condition is fully reset allowing immediate restart.
NOTE
NOTE:
When the "Reset Lockout Using Reset Key" setpoint is set to "Enabled," pressing the Reset
key will reset all Lockout and Non-Lockout trips. When a Lockout Reset is used to reset a
Thermal Overload, the Thermal Capacity % will be reset to zero.
6.3.1.7 Thermal protection setpoints
Select the Home > Setpoints > Protection > Thermal page to edit the thermal protection
setpoints.
0%
25%
50%
75%
100%
0 30 60 90 120 150 180
Time (minutes)
Cool time constant = 30 minutes
63%
Thermal capacity used
853732A1.CDR