Delta MM300 Instruction Manual Page 125

  • Download
  • Add to my manuals
  • Print
  • Page
    / 167
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 124
6–38 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
PROTECTION ELEMENTS CHAPTER 6: SETPOINTS
6.3.3 Electrical protection
6.3.3.1 Current unbalance protection
When an unbalance or phase current exceeds the setpoints, an alarm or trip condition is
generated.
The calculation method is as follows:
Current Unbalance Trip Level
Range: 4 to 40%, in steps of 1, or OFF
Default: 30%
This setpoint specifies the current unbalance trip pickup level. A value of “OFF” disables
the current unbalance trip function.
Current Unbalance Trip Delay
Range: 1 to 60 seconds in steps of 1
Default: 1 second
This setpoint specifies the time the motor unbalance current must meet or exceed
pickup to generate a trip.
Current Unbalance Alarm Level
Range: 4 to 40%, in steps of 1, or OFF
Default: 15%
This setpoint specifies the current unbalance alarm pickup level. A value of “OFF”
disables the current unbalance alarm function.
Current Unbalance Alarm Delay
Range: 1 to 60 seconds in steps of 1
Default: 1 second
This setpoint specifies the time the motor unbalance current must meet or exceed
pickup to generate an alarm.
6.3.3.2 Ground fault protection
When motor stator windings become wet or otherwise suffer insulation deterioration, low
magnitude leakage currents often precede complete failure and resultant destructive fault
currents. Ground fault protection provides early detection of such leakage current,
allowing the motor to be taken offline in time to limit motor damage. However, if a high
magnitude ground fault occurs that is beyond the capability of the contactor to interrupt,
it is desirable to wait for the fuses or an upstream device to provide the interruption.
The ground fault protection will alarm or trip when the ground current magnitude meets or
exceeds the pickup for the specified time, provided that the maximum phase current is less
than 8 × FLA. When used with a core-balance CT, this protection becomes a sensitive
ground fault protection.
A ground fault trip is a serious event, and therefore results in a lockout that can not be
reset until the motor has cooled except with a level 2 or level 3 security login.
Where:
I = average phase current
I = current in a phase with maximum deviation from I
I = MOTOR FULL LOAD CURRENT setpoint
AV
M AV
FLA
I
AV
IFLA
:
UB%
=
|I - I |
MAV
IAV
I
AV
IFLA
:
UB%
=
|I - I |
MAV
IFLA
× 100%
× 100%
If
If
Page view 124
1 2 ... 120 121 122 123 124 125 126 127 128 129 130 ... 166 167

Comments to this Manuals

No comments