CHAPTER 6: SETPOINTS CONFIGURATION SETPOINTS
MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–19
NOTE
NOTE:
When changing the IP address, power to the relay must be cycled in order for the new IP
address to become active.
Ethernet Subnet Mask
Range: standard IP address format
Default: 255.255.252.0
This setpoint specifies the subnet IP mask provided by the network administrator.
Ethernet Gateway Address
Range: standard IP address format
Default: 0.0.0.0
This setpoint specifies the gateway IP address provided by the network administrator.
NTP Address
This setpoint is set to the IP address of the external clock source.
Profibus Address
Range: 1 to 125
Default: 125
Specifies the Profibus Slave address for this node.
Profibus Baud Rate
Range: 9600, 19200, 31250, 45450, 93750, 187500, 500K, 1.5M, Autodetect
Default: Autodetect*
Specifies the speed of communication for the Profibus inteface.
* Profibus communications will operate only in 1.5Mbps or auto-detect with the
presentimplementation. Auto-detect includes all listed baud rates.
Comms OK Evaluation
Range: Serial, Serial + Ethernet, Serial + Fieldbus, Ethernet, Fieldbus, Ethernet + Fieldbus,
All
Default: Serial
Specifies the operands for the Comms OK flag.
Comm Failure Trip
Range: Off, 5 to 25 step 5s
Default: Off
Specifies the time without comms before a trip will be generated.
Comm Failure Alarm
Range: Off, 5 to 25 step 5s
Default: Off
Specifies the time without comms before an alarm will be generated.
NOTE
NOTE:
Timing delay commences after failure is detected.
Change Mode on Comm Alarm
Range: Disabled, Enabled
Default: Disabled
If enabled, forces control mode to manual if comms are lost.