Delta MM300 Instruction Manual Page 96

  • Download
  • Add to my manuals
  • Print
  • Page
    / 167
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 95
CHAPTER 6: SETPOINTS CONFIGURATION SETPOINTS
MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–9
Pre-contactor is omitted on forced starts (for example, undervoltage restart immediate or
external start). Otherwise, contactor A forced starts operate in the same fashion as other
contactor A starts, with the transfer to full voltage occurring when the transfer time
expires. Contactor B forced starts are not supervised by this starter transfer timer – any
external contactor B starting circuit must itself respect full voltage starting restrictions.
The following figure illustrates typical starter timing beginning from the stopped state.
Figure 7: Typical starter timing for wye-delta open transition starter
The following additional setpoints are available for the wye-delta open transition starter.
Pre-Contactor Time
Range: 0 to 60 seconds in steps of 1
Default: 0 seconds
This setpoint represents the time after a start command before the motor is started.
Most starters do not use this delay for forced starts such as undervoltage restart
immediate and external start. This setpoint is also used by the inverter starter and the
soft start starter to set the amount of time between powering up an inverter or soft
starter and sending the ramp-up command. An audible or other warning signal can be
activated in this interval by connecting the signal to a contact output set to the pre-
contactor function.
Transfer Time
Range: 0 to 125 seconds in steps of 1
Default: 1 second
If the value specified by this setpoint has expired, the transition from wye (contactor A) to
delta (contactor B) will occur.
6.2.1.6 Inverter starter
The “Inverter” starter type is used with an external inverter that ramps the motor speed up
on start and ramps it down on stop.
When a start A control is received, the contactor A relay picks up and seals-in. This
provides power for the inverter to start up and to drive the motor. The pre-contactor relay
(if any) is also picked up for the set
Pre-Contactor Time. When the pre-contactor timer
times out, the contactor B relay is picked up signalling the inverter to ramp the motor up.
When a stop control is received, the contactor A and B relays drop out immediately,
signalling the inverter to ramp down.
If the contactor B status unexpectedly opens while running, signalling a possible inverter
trouble, the contactor B relay is dropped out and an Inverter Trip Alarm is issued, but no
trip is issued and the contactor A relay remains closed. This is done so that the inverter has
power to retain its event records for subsequent diagnosis of the problem. The contactor A
relay is opened and the alarm is reset when a stop control is received.
Start A
Start B
Start A
Stop
Contactor B relay
Contactor A relay
Pre-contactor
Starting
Running
Motor current
P
T
P = Pre-contactor time setting
T =- Transfer time setting
853720A1.CDR
Page view 95
1 2 ... 91 92 93 94 95 96 97 98 99 100 101 ... 166 167

Comments to this Manuals

No comments