CHAPTER 6: SETPOINTS CONTROL ELEMENTS
MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–53
Figure 30: Process interlock timing
The following setpoints are available. The setpoints and logic for interlock A shown below
applies to all interlocks A through J.
[Path: Home > Setpoints > Control > Interlock]
IL A Function
Range: Disabled, Trip, Stop, Alarm
Default: Disabled
This setpoint selects whether the process interlock causes a trip (reset required to restart
the motor), a stop (no reset required), or alarms only. The “Disabled” selection disables all
interlock functions, including the instantaneous alarm.
IL A Healthy State
Range: Open, Closed
Default: Closed
This setpoint allows the user to configure the process interlock contact input as either
healthy open or healthy closed. The switch state is healthy when no action is taken by
this interlock.
Started
i.e.: Pre-contactor, Starting or Running
Not Started:
i.e.: Stopped, Stopping, Tripped, Locked
Out, Blocked, Starts Inhibited or Restart
In Progress
Startup Override == 0, Running Override == OFF
Healthy
Unhealthy
Startup Override == 0, Running Override == 0...3600 s
running
override
set time
running
override
set time
Action
starts inhibited
state irrelevant once started
Healthy
Unhealthy
Startup Override > 0, Running Override == OFF
startup override
set time
Action
Healthy
Unhealthy
state irrelevant after startup timeoutstate irrelevant before startup timeout
Startup Override > 0, Running Override == 0...3600 s
startup override
set time
Healthy
Unhealthy
state irrelevant before startup timeout
running
override
853703A1.CDR
running
override
set time
Action
starts inhibited