4–12 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
POWER ANALYSIS CHAPTER 4: SOFTWARE OPERATION
12. Use the graph attribute utility described in step 9, to change the vector colors.
4.2.2 Data logger
The data logger feature is used to sample and record up to ten actual values at a
selectable interval. The datalogger can be run with Continuous mode Enabled, which will
continuously record samples until stopped by the user; or with Continuous mode Disabled,
which will trigger the datalog once without overwriting previous data.
Viewing and saving of the Datalogger is performed as follows:
1. With EnerVista MM300 Setup running and communications established, select the
Diagnostics > Datalog menu item to open the datalog setup window:
2. If Continuous mode is enabled, click on Stop to stop the datalog
3. Click on the Save to File button to save the datalog to the local PC. A new window will
appear requesting for file name and path.
4. One file is saved as a COMTRADE file, with the extension ‘CFG’. The other file is a DAT
file, required by the COMTRADE file for proper display of data.
5. To view a previously saved COMTRADE file, click the Open button and select the
corresponding COMTRADE file.
6. To view the datalog, click the Launch Viewer button. A detailed Datalog window will
appear as shown below.
Setting Parameter
Sample Rate 1 Second
Continuous Mode Disabled
Data Log Trigger Position 25%
Data Log Trigger Source None
Channel 1 Source Phase A Current
Channel 2 Source Phase B Current
Channel 3 Source Phase C Current
Channel 4 Source Disabled
Channel 5 Source Disabled
Channel 6 Source Disabled
Channel 7 Source Disabled
Channel 8 Source Disabled
Channel 9 Source Disabled
Channel 10 Source Disabled