4.1.7 Motor Connection
MCD 500 soft starters can be connected to the motor in-line
or inside delta (also called three-wire and six-wire
connection). The MCD 500 will automatically detect the
motor connection and perform the necessary calculations
internally, so it is only necessary to program the motor full
load current (par. 1-1).
N
NOTE
For personnel safety, the power terminals on models up to
MCD5-0105B are protected by snap-off tabs. W
hen using
large cables, it may be necessary to break off these tabs.
Models which are internally bypass
ed do not require an
external bypass contactor.
4.2 In-Line Installation
4.2.1 In-line Installation, Internally Bypassed
177HA430.11
M
3
6/T3
2/T1
5/L3
3/L2
1/L1
13
14
4/T2
E
KM1
KM1 F1
KM1 Main contactor (optional)
F1 Fuses (optional)
4.2.2 In-line Installation, Non-bypassed
177HA429.11
6/T3
2/T1
5/L3
3/L2
1/L1
13
14
4/T2
E
KM1
KM1 F1
M
3
KM1 Main contactor (optional)
F1 Fuses (optional)
Electrical Installation MCD 500 Operating Instruction
MG.17.K3.02 - VLT
®
is a registered Danfoss trademark 13