Serial (RS-232/422/485) 5.5
Communications 5-253
Communication Command: From this drop-down list, select PLC-5 Typed Read
to read values from the RMC, or PLC-5 Typed Write to write values to the RMC.
Data Table Address: Enter the address of the first Allen-Bradley PLC register to
read RMC registers into, or to write to RMC registers from.
Size in Elements: Enter the number of RMC registers to read or write in this field.
Transfers are limited to 1000 bytes for PLC-5 Typed Reads and Writes. Therefore,
this limit is 500 integers, 250 floats, etc. Notice that this limit is larger than the
number of elements in the RMC's N-files. Reads or writes that extend beyond the
end of a register file will continue into the next register file. For example, reading
300 elements from N9:0 will read N9:0 to N9:255, then N10:0 to N10:43.
Port Number: Set this to the channel number of the serial port you want to use.
Target Device: This section holds parameters for the target device.
Data Table Address: Enter the address of the first RMC register to read or write in
this field. See the RMC Register Map (Allen-Bradley) for help on addresses.
MultiHop: This parameter should be set to No.
Local Node Addr (dec): Enter the node address of this RMC. The node address of
the RMC is set up in the Serial Module Options dialog box, which is described in
Configuring the RMC SERIAL. The node address entered on that screen is in
decimal, so it is recommended that you enter the same number in the dec field.
Allen-Bradley SLC 5/0x
The SLC 5/05 MSG block is displayed as the following:
Type: This parameter is always set to Peer-to-Peer for serial communication channels.
Read/Write: This parameter should be set to Read to read registers from the RMC, and to
Write to write registers to the RMC.
Target Device: This parameter has possible values of 500CPU, 485CIF, and PLC5. This
should be set to PLC5 or 500CPU for communicating with the RMC.
Local/Remote: This parameter has possible values of Local and Remote. This will be set to
Local when the RMC is on the same serial network as the SLC.
Control Block: This parameter points to a block of 12 integer-file registers. Set this to a
block of registers, and then use the Setup Screen option in the MSG ladder logic block to
modify those register values: