IQ 100 Series (130/140/150) Meter
Overview &Specifications
18 User and Installation Manual IM02601003E-September 2011 www.eaton.com
Accuracy
For 23
0
C, 3 Phase balanced Wye or Delta load, at 50 or 60 Hz (as per order), 5A (Class 10)
nominal unit.
Parameters Accuracy Accuracy Input Range
Voltage L-N [V] 0.25% of reading
2
(69 to 480)V
Voltage L-L [V] 0.25% of reading (120 to 600)V
Current Phase [A] 0.25% of reading
1
(0.15 to 5)A
Current Neutral (Calculated) [A] 2.0% of reading
1
(0.15 to 5)A @ (45 to 65)Hz
Active Power Total [W] 0.5% of reading
1,2
(0.15 to 5)A@(69 to 480)V@+/- (0.5 to 1)lag/lead PF
Active Energy Total [Wh] 0.5% of reading
1,2
(0.15 to 5)A@(69 to 480)V@+/- (0.5 to 1)lag/lead PF
Reactive Power Total [VAR] 0.5% of reading
1,2
(0.15 to 5)A@(69 to 480)V@+/- (0 to 0.8)lag/lead PF
Reactive Energy Total [VARh] 0.5% of reading
1,2
(0.15 to 5)A@(69 to 480)V@+/- (0 to 0.8)lag/lead PF
Apparent Power Total [VA] 0.5% of reading
1,2
(0.15 to 5)A@(69 to 480)V@+/- (0.5 to 1)lag/lead PF
Apparent Energy Total [VAh] 0.5% of reading
1,2
(0.15 to 5)A@(69 to 480)V@+/- (0.5 to 1)lag/lead PF
Power Factor 0.5% of reading
1,2
(0.15 to 5)A@(69 to 480)V@+/- (0.5 to 1)lag/lead PF
Frequency +/- 0.01 Hz (45 to 65) Hz
% of Load Bar +/- 1 segment (0.005 to 6)A
1
For 2.5 element programmed units, degrade accuracy by an additional 0.5% of reading.
- For 1A (Class 2) Nominal, degrade accuracy by an additional 0.5% of reading.
- For 1A (Class 2) Nominal, the input current range for Accuracy specication is 20% of
the values listed in the table.
2
For unbalanced voltage inputs where at least one crosses the 150V auto-scale threshold (for
example, 120V/120V/208V system), degrade accuracy by additional 0.4%.