IQ 100 Series ((130/140/150) Meter
App B: Modbus Map
User and Installation Manual IM02601003E - September 2011 www.eaton.com 81
App.B: Modbus Mapping for the IQ 100 Series
Introduction
The Modbus map for the IQ 100 Series meter gives details and information about the possible readings
of the meter and its programming.
Modbus Register Map Sections
The IQ 100 Series Modbus register map includes the following sections:
Fixed Data Section, Registers 1- 47, details the meter’s Fixed Information.
Meter Data Section, Registers 1000 - 12031, details the meter’s readings, including Primary readings,
Energy Block, Demand Block (IQ 140/150 meter), Phase Angle Block, Status Block, and Minimum and
Maximum readings.
Commands Section, Registers 20000 - 26011, details the meter’s Resets Block, Programming Block,
Other Commands Block and Encryption Block.
Programmable Settings Section, Registers 30000 - 33575, details all the setups you can program to
congure your meter.
Secondary Readings Section, Registers 40001 - 40100, details the meter’s Secondary readings.
Data Formats
ASCII:
ASCII characters packed 2 per register in high, low order and without any
termination characters.
SINT16/UINT16: 16-bit signed/unsigned integer.
SINT32/UINT32: 32-bit signed/unsigned integer spanning 2 registers. The lower-addressed
register is the high order half.
FLOAT: 32-bit IEEE oating point number spanning 2 registers. The lower-addressed
register is the high order half (i.e., contains the exponent).