IQ 100 Series ((130/140/150) Meter
Communication Installation
User and Installation Manual IM02601003E - September 2011 www.eaton.com 47
(Example: Setting device with static IP Address.)
IP Address <010> 192.<000> 168.<000> .<000> .<001>
Set Gateway IP Address <N>? Y
Gateway IP Address: <192> .<168> .<000> .<001>
Set Netmask <N for default> <Y>? Y
6. Continue setting up parameters as needed. When you nish your modications, make sure to press
the “S” key on the keyboard. This saves the new values and causes a Reset in the Ethernet card.
CAUTION! DO NOT PRESS ‘D’ as it will overwrite any changes and save the default values.
IMPORTANT! If the IP Address of the Ethernet card is lost, you can restore the factory default settings
by pressing the Reset button on the card. Follow the procedure below.
Resetting the Ethernet Card
The Ethernet card’s Reset button is accessed from the back of the IQ 100 Series meter. See the gure
below.
Using an implement such as a ballpoint pen tip, press and hold the Reset button for 30 seconds. The
Ethernet card is reset to the default settings shown on the previous page.
Reset Button