IQ 100 Series (130/140/150) Meter
Programming the IQ 100 Series Using Software
71 User and Installation Manual IM02601003E-September 2011 www.eaton.com
Performing Additional Tasks with Eaton Meter Conguration Software
The following sections contain instructions for other tasks you can perform using the Eaton Meter
Conguration software.
Using Connection Manager
Use Connection Manager to add or remove connection
locations and/or devices at locations.
1. Click Connection>Connection Manager or click on the
Connect Mgr icon. You will see the screen shown on
the right.
List of Locations:
On the left side of the Connection Manager screen is a List
of Locations. These are the locations of one or more
meters to which you can connect. You can add a location
and/or a device; edit a location and/or device; or remove
a location and/or device.
• To add a location:
a. Click on the Add button. You will see the Connection
Manager Location Editor screen. On this screen,
you program the Communication settings for each
new location.
b. Type a name for the new location.
c. Click Serial Port or Network.
d. Enter Communication settings:
Com Port: COM 1 - 99
Baud Rate: 1200 - 115200
Flow Control: None or Hardware
Data Bits: 8 (or 7)
Parity: None (Even, Odd)
e. To add a device:
- Click Add Serial (to add a Serial Port connected
device) or Add Net (to add a Network connected device) in the Devices at Location box. You
can add up to 255 devices (Serial Port and/or Network connected) at one location.
NOTES:
• All devices must have the same connection parameters: Baud, Parity and Flow Control.
• Multiple devices slow down polling.