POWER MONITORING & PROTECTION
POWER MONITORING & PROTECTION
16
WE MAKE IT EASY.
kele.com 888-397-5353 USA
E50 SERIES POWER METER
E50 SERIES
Supply Voltage
UL 90 VAC (L-N) to 600 VAC (L-L),
50/60Hz
CE 90 VAC (L-N) to 300 VAC (L-L),
50/60Hz, UL 90 VAC (L-N) to
600 VAC (L-L), 50/60Hz
Monitored Voltage Line to Line: 90 to 600 VAC
Line to Line with
Potential Transformer 601 to 32000 VAC
Monitored Current 5 to 32,000 Amps
Current Transformer
Input 0 to 0.333V to 0 to 1 V
Input Signal 2 (E50H5 only) Pulse Solid-State
or mechanical contacts (current less
than 1 mA) Minimum Pulse Width
20 msec
Outputs
E50B1 Reactive energy pulse 30 VAC/DC,
E50C1 RS-485 2-wire Modbus RTU Basic
Data Set
E50C2/E51C2 RS-485 2-wire, Modbus RTU Full
Data Set,
E50C3/E51C3 RS-485 2-wire Modbus RTU Full
Data Set, data logging,
E50H3 RS-485 2-wire BACnet MS/TP Full
Data Set, data logging
Accuracy Real power and energy 0.5% (ANSI
C12.20, IEC 62053-22 Class 0.5S)
Operating Temperature
Meter: -22° to 158°F (-30° to 70°C)
Display: 14° to 122°F (-10° to 50°C)
Operating Humidity < 95% RH non-condensing
Mounting DIN Rail or 3-point screw mount
Dimensions 2.3" x 4.2" x 3.6"
(5.9 cm x 10.7 cm 9.1 cm)
Weight 0.62 lb (0.28 kg)
Approvals CE, UL508, File #E339785,
RoHS Statement Ye s
Warranty 5 years
DESCRIPTION
The E50 Series power meter provides a solution for
measuring energy data with a single device. Inputs include
Control Power, CT, and 3-phase voltage. The E50 supports
multiple output options, including solid state relay contacts,
BACnet, Modbus RTU (with or without data logging), and
pulse. The LCD screen on the faceplate allows instant output
viewing. The meter is housed in a plastic enclosure suitable
for installation on T35 DIN rail according to EN50022. The
E50 can be mounted with any orientation over the entire
ambient temperature range, either on a DIN rail or in a
panel. The meter is not sensitive to CT orientation to reduce
installation errors.
FEATURES
Monitors 1, 2, or 3 phase services
Monitors services up to 600 VAC directly and 32,000
VAC with use of a potential transformer
Accepts .333 VAC or 1V Current Transformer's (sold
separately)
DIN mounting for easy installation
ANSI 12.20 0.5% accuracy
BACnet, Modbus RTU or pulse output
90-600 VAC for application versatility
Bright backlit LCD with easy visibility
Pulse and phase loss alarms standard
User-enabled password protection
Approved for California Solar applications
DIMENSIONS
SPECIFICATIONS
E50
3.6
(9.1)
4.2 (10.7)
0.2
(0.4)
3.9
(9.9)
2.4 (6.1)
++
+
4.3
(10.9)
1.2
(3.1)
0.3
(0.8)
0.4 (1.0)
DIN Mount Option
Screw Mount Option
TM
March 2014