SPLIT-CORE CURRENT TRANSFORMERS
600T, 601T
Secondary 0-5A
Frequency 50-400 Hz
Insulation Class 600V, 10 kV BIL Full Wave
Continuous Thermal
Current Resistor Factor 1.33 @ 30°C (86°F) ambient 1.0
@ 55°C (131°F) ambient
Terminations Brass stud terminals with nut, flat
washer, lockwasher
Materials Of Construction
Plastic, UL94V-1
Window Size 2.0" x 5.5" (5.08 x 13.97 cm),
4.5" x 4.5" (11.43 x 11.43 cm)
Weight 1.5 lb (0.68 kg)
Approvals UL-recognized component,
File #E238872; CSA certified,
File #245941
Warranty 1 year
A
D
1.13
(2.87)
C
B
0.44
(1.12)
Two Mounting Holes
0.19 (0.48) dia
LABEL
601
6.75 (17.15)
4.50 (11.43)
4.50 (11.43)
6.75 (17.15)
DIMENSIONS
MODEL
A
B
C
D
X1
H1
This End
Removable
600
7.75 (19.69)
5.50 (13.97)
2.00 (5.08)
4.25 (10.80)
in
(cm)
DESCRIPTION
The Model 600T and 601T Split-Core Current Transformers
provide a low amperage current output proportional to line
current. They are for use in energy management control
and metering applications, and are ideal for use as inputs to
power monitors like the EnGenius™ and current transducers
like Models 4CTV and 4CMA.These transformers are
designed to be assembled around an existing insulated
conductor without the need for dismantling the primary bus
or cables. The portion of the transformers marked "This End
Removable" can be disassembled and then reassembled
around the conductors that require current monitoring.
FEATURES
5A secondary
Split-core construction for easy installation
Brass stud terminals #8-32 with one flat washer,
lockwasher and regular nut
DIMENSIONS
SPECIFICATIONS
601T
(shown with end removed)
ORDERING INFORMATION
CURRENT RATIO
1200/800:5
MODEL 600T - 2.0" x 5.5" (5.1 x 14 cm) Window
MODEL CURRENT
RATIO
B0.1
2.5 VA
B0.2
5 VA
B0.5
12.5 VA
ANSI METER CLASS @ 60 Hz
ANSI METER CLASS @ 60 Hz
MULTI RATIO
600T-122-801
ACCURACY CLASS
WITH UNITY POWER FACTOR
4.8
4.8
2.4
1.2
1.2
1.2
0.6
0.6
2.4
2.4
2.4
1.2
1.2
0.6
0.6
0.6
400:5
500:5
600:5
800:5
1000:5
1200:5
1600:5
2000:5
600T-401
600T-501
600T-601
600T-801
600T-102
600T-122
600T-162
600T-202
± 1% @ 1.5 VA
± 1% @ 2.0 VA
± 1% @ 2.5 VA
± 1% @ 5.0 VA
± 1% @ 7.5 VA
± 1% @ 15.0 VA
± 1% @ 20.0 VA
± 1% @ 30.0 VA
--
--
--
2.4
2.4
1.2
1.2
0.6
MODEL CURRENT
RATIO
B0.1
2.5 VA
B0.2
5 VA
B0.5
12.5 VA
--
--
4.8
4.8
2.4
1.2
1.2
1.2
1.2
0.6
--
--
--
--
4.8
4.8
2.4
1.2
1.2
1.2
601T-301
601T-401
601T-501
601T-601
601T-801
601T-102
601T-122
601T-152
601T-162
601T-202
MODEL 601T - 4.5" x 4.5" (11.4 x 11.4 cm) Window
ACCURACY CLASS
WITH UNITY POWER FACTOR
± 1% @ 0.5 VA
± 1% @ 1.0 VA
± 1% @ 1.5 VA
± 1% @ 2.0 VA
± 1% @ 2.5 VA
± 1% @ 5.0 VA
± 1% @ 10.0 VA
± 1% @ 15.0 VA
± 1% @ 15.0 VA
± 1% @ 20.0 VA
300:5
400:5
500:5
600:5
800:5
1000:5
1200:5
1500:5
1600:5
2000:5
--
4.8
4.8
2.4
1.2
1.2
1.2
1.2
1.2
0.6
CURRENT RATIO
1200/800/400:5
MULTI RATIO
601T-122-MR
CAUTION: Proper safety precautions must be followed
by a trained electrician during installation. It is
recommended that the incoming power be deenergized
before installation. The current transformer must have its
secondary terminals short-circuited or the burden (load)
connected before energizing the primary circuit. For
indoor use only. Use on insulated conductor only.
Example: 601T-102 Split-core current transformer with a current ratio of 1000:5 and a window size of 4.5" x 4.5" (11.4 x 11.4 cm)
March 2014