IQ 100 Series (130/140/150) Meter Appendix B: Modbus Map
Description
1
Format Range
6
Units or
Resolution Comments
#
Reg
Modbus Address
Hex Decimal
7548 - 7548 30025 - 30025 Reserved 1
7549 - 7549 30026 - 30026 COM2 setup UINT16 bit-mapped
----dddd -ppp-bbb
1
754A - 754A 30027 - 30027 COM2 address UINT16 1 to 247 none 1
754B - 754B 30028 - 30028 Reserved 1
754C - 754C 30029 - 30029 Reserved 1
754D - 754D 30030 - 30030 Reserved 1
754E - 754E 30031 - 30031 Reserved 1
754F - 754F 30032 - 30032 Reserved 1
7550 - 7554 30033 - 30037 5
7555 - 7559 30038 - 30042 5
755A - 755E 30043 - 30047 5
755F - 7563 30048 - 30052 5
7564 - 7568 30053 - 30057 5
7569 - 756D 30058 - 30062 5
756E - 7572 30063 - 30067 5
Block Size
:
68
read-only except as noted
9C40 - 9C40 40001 - 40001 System Sanity Indicator UINT16 0 or 1 none
0 indicates proper meter operatio
1
9C41 - 9C41 40002 - 40002 Volts A-N UINT16 2047 to 4095 volts 2047= 0, 4095= +150 1
9C42 - 9C42 40003 - 40003 Volts B-N UINT16 2047 to 4095 volts 1
9C43 - 9C43 40004 - 40004 Volts C-N UINT16 2047 to 4095 volts 1
9C44 - 9C44 40005 - 40005 Amps A UINT16 0 to 4095 amps
0= -10, 2047= 0, 4095= +10
1
9C45 - 9C45 40006 - 40006 Amps B UINT16 0 to 4095 amps 1
9C46 - 9C46 40007 - 40007 Amps C UINT16 0 to 4095 amps 1
9C47 - 9C47 40008 - 40008 Watts, 3-Ph total UINT16 0 to 4095 watts 0= -3000, 2047= 0, 4095= +3000 1
9C48 - 9C48 40009 - 40009 VARs, 3-Ph total UINT16 0 to 4095 VARs watts, VARs, VAs = 1
9C49 - 9C49 40010 - 40010 VAs, 3-Ph total UINT16 2047 to 4095 VAs
3000 * (register - 2047) / 2047
1
9C4A - 9C4A 40011 - 40011 Power Factor, 3-Ph total UINT16 1047 to 3047 none
1047= -1, 2047= 0, 3047= +1
pf = (register - 2047) / 1000
1
9C4B - 9C4B 40012 - 40012 Frequency UINT16 0 to 2730 Hz 0= 45 or less, 2047= 60, 2730= 65 or more
freq = 45 + ((register / 4095) * 30)
1
9C4C - 9C4C 40013 - 40013 Volts A-B UINT16 2047 to 4095 volts 2047= 0, 4095= +300 1
9C4D - 9C4D 40014 - 40014 Volts B-C UINT16 2047 to 4095 volts 1
9C4E - 9C4E 40015 - 40015 Volts C-A UINT16 2047 to 4095 volts 1
dddd = reply delay (* 50 msec)
ppp = protocol (1-Modbus RTU, 2-Modbus
ASCII, 3-DNP)
amps = 10 * (register - 2047) / 2047
12-Bit RTU Readin
g
s Section
12-Bit RTU Block
volts = 150 * (register - 2047) / 2047
volts = 300 * (register - 2047) / 2047