Delta AH500 series Manual Page 89

  • Download
  • Add to my manuals
  • Print
  • Page
    / 297
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 88
AH500 Hardware Manual
Digital-to-analog
conversion
Current output
Rated output
range
0 mA~20 mA 4 mA~20 mA
Hardware output
range
-0.2 mA~20.2 mA 3.8 mA~20.2 mA
Fiducial error
(Room
temperature) (The
number of output
currents which are
averaged is 100.)
±0.06%
Fiducial error (Full
temperature
range) (The
number of output
currents which are
averaged is 100.)
±0.07%
Linearity error
(Room
temperature)
±0.01%
Linearity error
(Full temperature
range)
±0.01%
Hardware
resolution
16 bits
Permissible load
impedance
550
3.6.2 Profiles
AH04AD-5A/AH08AD-5B/AH08AD-5C/AH04DA-5A/AH08DA-5B/AH08DA-5C/AH06XA-5A
RUN
ERROR
04AD
SG
ZP
UP
-10~+10V
-20~+20mA
VI0
I3
VI3
I1
I2
V3
VI2
V2
V1
VI1
I0
V0
1
2
3
4
7
6
8
9
10
5
Number Name Description
1 Model name Model name of the module
2 RUN LED indicator
Operating status of the module
ON: The module is running.
OFF: The module stops running.
3-45
Page view 88
1 2 ... 84 85 86 87 88 89 90 91 92 93 94 ... 296 297

Comments to this Manuals

No comments