AH06XA-5A
±10V,±20mA
±10V,0/4~20mA
AI
06XA
RUN
ERROR
AO
ZP
UP
SG
VI0
AG
IO1
VO1
VO0
IO0
VI3
I3
I1
I2
V3
VI2
V2
V1
VI1
I0
V0
3.7 Specifications for Temperature Measurement Modules
3.7.1 General Specifications
AH04PT-5A
Electrical specifications
Number of analog
inputs
4
Three-wire configuration: Pt100/Ni100/Pt1000/Ni1000 sensor, and 0~300
input impedance
Applicable sensor
Two-wire/Four-wire configuration: Pt100/Ni100/Pt1000/Ni1000 sensor, and
0~300 input impedance
Pt100: DIN 43760-1980 JIS C1604-1989; 100 3850 PPM/°C
Pt1000: DIN EN60751; 1 k 3850 PPM/°C
Ni100/Ni1000: DIN 43760
Supply voltage 24 V DC (20.4 V DC~28.8 V DC) (-15%~+20%)
Connector type Removable terminal block
25°C/77°F
: The error is 0.5% of the input within the range.
Overall accuracy
-20~60°C/-4~140°F: The error is 1% of the input within the range.
Conversion time
Two-wire/Four-wire configuration: 150 ms/channel
Three-wire configuration: 300 ms/channel
Isolation
An analog circuit is isolated from a digital circuit by a digital integrated circuit/an
optocoupler, and the analog channels are isolated from one another by
optocouplers.
Isolation between a digital circuit and a ground: 500 V DC
Isolation between an analog circuit and a ground: 500 V DC
Isolation between an analog circuit and a digital circuit: 500 V DC
Isolation between the 24 V DC and a ground: 500 V DC
3-48