Delta AH500 series Manual Page 87

  • Download
  • Add to my manuals
  • Print
  • Page
    / 297
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 86
AH500 Hardware Manual
AH06XA-5A
Electrical specifications
Module name AH06XA-5A
Number of inputs 4
Number of outputs 2
Analog-to-digital
conversion
Voltage input/Current input/Voltage output/Current output
Supply voltage 24 V DC (20.4 V DC~28.8 V DC) (-15%~+20%)
Connector type Removable terminal block
Conversion time 150 us/channel
An analog circuit is isol
ated from a digital circuit by a digital integrated circuit/an
optocoupler, but the analog channels are not isolated from one another.
Isolation
Isolation between a digital circuit and a ground: 500 V DC
Isolation between an analog circuit and a ground: 500 V DC
Isolation between an analog circuit and a digital circuit: 500 V DC
Isolation between the 24 V DC and a ground: 500 V DC
Functional specifications for the analog-to-digital conversion
Analog-to-digital
conversion
Voltage input
Rated input range -10 V~10 V 0 V~10 V ±5 V 0 V~5 V 1 V~5 V
Hardware input
range
-10.1 V~10.1 V -0.1 V~10.1 V -5.05 V~5.05 V -0.05 V~5.05 V 0.95 V~5.05 V
Fiducial error
(Room
temperature) (The
number of input
voltages which are
averaged is 100.)
±0.1%
Fiducial error (Full
temperature
range) (The
number of input
voltages which are
averaged is 100.)
±0.45%
Linearity error
(Room
temperature)
±0.07%
Linearity error
(Full temperature
range)
±0.12%
Hardware
resolution
16 bits
Input impedance >200 k
Absolute input
range
±15 V
Analog-to-digital
conversion
Current input
Rated input range ±20 mA 0 mA~20 mA 4 mA~20 mA
Hardware input
range
-20.2 mA~20.2 mA -0.2 mA~20.2 mA 3.8 mA~20.2 mA
3-43
Page view 86
1 2 ... 82 83 84 85 86 87 88 89 90 91 92 ... 296 297

Comments to this Manuals