Appendix A
A-6 DVP-MC operating manual
Note:
1. It is suggested that the two ends of the bus should be connected with one resistor of the value: 120
respectively.
2. To ensure the communication quality , the double shielded and twisted-pair cable is recommended
20AWG.
3. When the internal voltages of two devices are different, make SGSignal Groundof the two device
connected with each other to balance their SG voltages and make the communication more stable.
ASCII Mode
1. Communication data structure
Field name Components Explanation
Start character STX Start character :“:”, the corresponding ASCII code: 0x3A
ADR 1
Communication
address
ADR 0
Communication address consists of two ASCII codes.
CMD 1
Function code
CMD 0
Function code consists of two ASCII codes.
DATA 0
DATA 1
……….
Data
DATA n-1
Data content consists of 2n ASCII codes, n205.
LRC CHK 1
LRC Check
LRC CHK 0
LRC check consists of two ASCII codes.
END1
End character
END0
End character consists of two ASCII codes.
END1 = CR 0x0D
END0 = LF 0x0A
The corresponding relation between hexadecimal character and ASCII code:
Hexadecimal
character
“0“ “1“ “2“ “3“ “4“ “5“ “6“ “7“
ASCII code 0x30 0x31 0x32 0x33 0x34 0x35 0x36 0x37
Hexadecimal
character
“8“ “9“ “A“ “B“ “C“ “D“ “E“ “F“
ASCII code 0x38 0x39 0x41 0x42 0x43 0x44 0x45 0x46
2. ADR (Communication address)
The valid range of communication address:0254.
Communication address: 0 means the broadcast message is sent to all slaves and the slaves which have
received the message will not make any response. If communication address is not 0, slaves will respond
to master after receiving the message normally. For instance, ASCII codes for the communication address
of 16 are denoted below.