Appendix A
A-4 DVP-MC operating manual
Table 2
D6516 bit
no.
Explanation D6516 Communication format setting
b3~b0=0000(H0)
Data bits =7, Parity =E, Stop bits =1
b3~b0=0001(H1)
Data bits =7, Parity=O, Stop bits =1
b3~b0=0010(H2)
Data bits =7, Parity =N, Stop bits =1
b3~b0
Communication
format
b3~b0=0100(H4) Data bits =8,Parity =N, Stop bits =2
9600bps
b7~b4=0000(H0)
b7~b4=0001(H1)
19200bps
b7~b4=0010(H2)
38400bps
b7~b4=0011(H3)
57600bps
b7~b4
Baud rate
b7~b4=0100(H4)
115200bps
b15~b8
Communication
address
b15~b8=00000010(H2)
Communication address is 2
¾ Example 1: the method of revising COM1 communication format.
To revise COM1 communication format, add the following program codes to the WPLSoft software. When
DVP10MC11T turns from STOP to RUN, PLC would detect if M1138 is on in the first scan cycle. If M1138
is on, the setting of COM1 will be revised according to D1036 value. In the following graph, COM1
communication format is revised into ASCII mode, 115200bps(Baud rate), 7(Data bits), E(Parity),
1 (Stop bits).
¾ Example 2: the method of revising COM2 communication format (COM2 is possessed by PLC).
To revise COM2 communication format, add following program codes to WPLSoft software. When
DVP10MC11T turns from STOP to RUN, PLC would detect if M1120 is on in the first scan cycle. If M1120
is on, the setting of COM2 will be revised according to D1120 value. In the following graph, COM2
communication format is revised into ASCII mode, 57600bps(Baud rate), 7(Data bits), E(Parity), 1
(Stop bits).